Assessment Year | 2014 |
---|---|
Principal Product | Electronic Housing and Heat Control Devices |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 95 |
Plant Area |
19,000
ft2
|
Annual Production | 10,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $273,057 | 3,388,606 |
kWh
|
$0.081 |
Electricity Demand | $224,760 | 8,449 |
kW-mo/yr
|
$26.60 |
Electricity Fees | $32,434 | - |
|
- |
Natural Gas | $11,407 | 1,534 |
MMBtu
|
$7.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $151,606 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,267 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $111,951 | $87,500 |
$66,706
827,621
kWh
|
$71,501
-
kW-mo/yr
|
$(-26,256.0)
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,136 | $45,100 |
$12,129
150,504
kWh
|
$8,007
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,196 | $1,300 |
$5,278
65,492
kWh
|
$1,918
-
kW-mo/yr
|
- | |
04 | 2.6241: Reduce temperature of process equipment when on standby | $6,896 | $400 |
$6,896
85,554
kWh
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,758 | $300 |
$2,758
34,219
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $1,388 | $4,600 |
$738
9,157
kWh
|
$650
-
kW-mo/yr
|
- | |
07 | 2.7134: Use photocell controls | $1,281 | $3,700 |
$1,100
13,646
kWh
|
$181
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $151,606 | $142,900 |
$95,605
1,186,193
kWh
|
$82,257
-
kW-mo/yr
|
$(-26,256.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $38,267 | $50,800 |
$28,161
349,415
kWh
|
$10,106
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs