Assessment Year | 2013 |
---|---|
Principal Product | vegetables |
NAICS | 424480: Fresh Fruit and Vegetable Merchant Wholesalers |
SIC | 5148: Fresh Fruits and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 450 |
Plant Area |
71,000
ft2
|
Annual Production | 10,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $283,282 | 4,128,415 |
kWh
|
$0.069 |
Electricity Demand | $147,583 | 7,970 |
kW-mo/yr
|
$18.52 |
Natural Gas | $1,328 | 149 |
MMBtu
|
$8.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $110,882 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,671 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7425: Clean or color roof to reduce solar load | $37,421 | $53,250 |
$37,421
545,502
kWh
|
- | - | - | |
02 | 2.4323: Use optimum size and capacity equipment | $23,156 | $8,740 |
$16,904
246,415
kWh
|
$6,252
-
kW-mo/yr
|
- | - | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $15,384 | $50,200 |
$12,982
189,247
kWh
|
$2,402
-
kW-mo/yr
|
- | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,246 | $10,350 |
$8,646
126,013
kWh
|
$1,600
-
kW-mo/yr
|
- | - | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $10,014 | $15,500 |
$3,775
55,022
kWh
|
$8,210
-
kW-mo/yr
|
$(-1,971.0)
-
MMBtu
|
- | |
06 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $7,769 | $7,320 |
$7,769
113,247
kWh
|
- | - | - | |
07 | 2.3132: Recharge batteries on during off-peak demand periods | $3,825 | $1,500 | - |
$1,672
-
kW-mo/yr
|
- | $2,153 | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,817 | $600 |
$1,817
26,488
kWh
|
- | - | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,250 | $200 |
$1,142
16,644
kWh
|
$108
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $110,882 | $147,660 |
$90,456
1,318,578
kWh
|
$20,244
-
kW-mo/yr
|
$(-1,971.0)
-
MMBtu
|
$2,153 | ||
TOTAL IMPLEMENTED | $38,671 | $53,450 |
$38,563
562,146
kWh
|
$108
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs