Assessment Year | 1997 |
---|---|
Principal Product | commercial turf equipment |
NAICS |
n/a
|
SIC | 3523: Farm Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 155 |
Plant Area |
136,616
ft2
|
Annual Production | 6,500
pieces
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $49,357 | 1,876,319 |
kWh
|
$0.026 |
Electricity Demand | $46,674 | 5,724 |
kW-mo/yr
|
$8.15 |
Natural Gas | $31,172 | 10,928 |
MMBtu
|
$2.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,650 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,590 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,680 | $27,070 |
$1,630
61,841
kWh
|
$2,050
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $2,490 | $6,950 | - | - |
$2,490
-
MMBtu
|
- | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,270 | $190 |
$1,140
43,083
kWh
|
$1,130
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.1133: Adjust burners for efficient operation | $660 | $1,000 |
$660
70,340
kWh
|
- | - | - | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $1,350 | $4,950 |
$780
29,894
kWh
|
$570
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $460 | $210 |
$50
21,102
kWh
|
$410
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7135: Install occupancy sensors | $140 | $800 |
$140
5,862
kWh
|
- | - | - | - | - | |
08 | 3.5316: Contract a wood pallet recycling company | $(-3,710.0) | $5,000 | - | - | - | - |
$3,120
-
lb
|
$(-6,830.0) | |
09 | 3.4116: Meter recycled water (to reduce sewer charges) | $5,310 | $100 | - | - | - |
$5,310
-
Tgal
|
- | - | |
TOTAL RECOMMENDED | $12,650 | $46,270 |
$4,400
232,122
kWh
|
$4,160
-
kW-mo/yr
|
$2,490
-
MMBtu
|
$5,310
-
Tgal
|
$3,120
-
lb
|
$(-6,830.0) | ||
TOTAL IMPLEMENTED | $10,590 | $40,960 |
$4,350
211,020
kWh
|
$3,750
-
kW-mo/yr
|
$2,490
-
MMBtu
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs