Assessment Year 2013
Principal Product Medical Devices
NAICS 339112: Surgical and Medical Instrument Manufacturing
SIC 3841: Surgical and Medical Instruments and Apparatus
Sales Range $100
M
to 500
M
# of Employees 458
Plant Area 82,800
ft2
Annual Production 50,000
pieces
Production Hrs. Annual 5,400
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $375,963 3,844,129
kWh
Electricity Demand $121,935 9,274
kW-mo/yr
Electricity Fees $49,790 -
Natural Gas $13,558 1,977
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $138,055 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7233: Use properly designed and sized hvac equipment $66,411 $232,360 $46,110
471,471
kWh
$20,301
-
kW-mo/yr
02 2.7232: Replace existing hvac unit with high efficiency model $40,710 $144,156 $36,642
374,659
kWh
$4,068
-
kW-mo/yr
03 2.7425: Clean or color roof to reduce solar load $17,415 $62,100 $17,415
178,069
kWh
-
04 2.4231: Reduce the pressure of compressed air to the minimum required $4,331 $600 $4,331
44,287
kWh
-
05 2.4239: Eliminate or reduce compressed air usage $4,263 $1,275 $4,263
43,591
kWh
-
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,508 $1,300 $3,354
34,295
kWh
$154
-
kW-mo/yr
07 2.7145: Install skylights $867 $2,400 $546
5,587
kWh
$321
-
kW-mo/yr
08 2.7134: Use photocell controls $550 $740 $479
4,897
kWh
$71
-
kW-mo/yr
TOTAL RECOMMENDED $138,055 $444,931 $113,140
1,156,856
kWh
$24,915
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs