Assessment Year | 2013 |
---|---|
Principal Product | Stamped Metal Products |
NAICS | 332119: Metal Crown, Closure, and Other Metal Stamping (except Automotive) |
SIC | 3469: Metal Stampings, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 182 |
Plant Area |
527,031
ft2
|
Annual Production | 50,000,000
pieces
|
Production Hrs. Annual | 6,321
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $167,429 | 1,911,368 |
kWh
|
$0.088 |
Electricity Demand | $94,544 | 6,108 |
kW-mo/yr
|
$15.48 |
Electricity Fees | $21,612 | - |
|
- |
Natural Gas | $12,113 | 1,786 |
MMBtu
|
$6.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $42,735 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,895 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,895 | $27,250 |
$7,409
84,581
kWh
|
$2,486
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,189 | $1,500 |
$5,749
65,628
kWh
|
$1,440
-
kW-mo/yr
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,453 | $11,325 |
$4,362
49,797
kWh
|
$1,091
-
kW-mo/yr
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,360 | $6,450 |
$3,812
43,516
kWh
|
$1,548
-
kW-mo/yr
|
|
05 | 2.7134: Use photocell controls | $4,384 | $5,920 |
$3,754
42,859
kWh
|
$630
-
kW-mo/yr
|
|
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,852 | $200 |
$3,852
43,971
kWh
|
- | |
07 | 2.7135: Install occupancy sensors | $3,360 | $3,887 |
$3,360
38,353
kWh
|
- | |
08 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,686 | $400 |
$1,262
14,412
kWh
|
$424
-
kW-mo/yr
|
|
09 | 2.7224: Reduce space conditioning during non-working hours | $1,556 | $500 |
$1,556
29,052
kWh
|
- | |
TOTAL RECOMMENDED | $42,735 | $57,432 |
$35,116
412,169
kWh
|
$7,619
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $9,895 | $27,250 |
$7,409
84,581
kWh
|
$2,486
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs