Assessment Year | 2013 |
---|---|
Principal Product | Air Conditioning Enclosures |
NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
Sales Range | $10 M to 50M |
# of Employees | 166 |
Plant Area |
100,000
ft2
|
Annual Production | 5,000
pieces
|
Production Hrs. Annual | 4,264
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,257 | 695,374 |
kWh
|
$0.13 |
Electricity Demand | $43,039 | 3,324 |
kW-mo/yr
|
$12.95 |
Electricity Fees | $3,325 | - |
|
- |
Natural Gas | $14,084 | 2,097 |
MMBtu
|
$6.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,092 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,768 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,304 | $1,500 |
$3,383
26,954
kWh
|
$921
-
kW-mo/yr
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,131 | $6,224 |
$3,248
25,881
kWh
|
$883
-
kW-mo/yr
|
|
03 | 2.7134: Use photocell controls | $2,625 | $1,850 |
$2,034
16,210
kWh
|
$591
-
kW-mo/yr
|
|
04 | 2.7132: Install timers on light switches in little used areas | $2,768 | $2,210 |
$2,768
22,049
kWh
|
- | |
05 | 2.7425: Clean or color roof to reduce solar load | $2,233 | $5,250 |
$2,233
17,792
kWh
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $564 | $200 |
$564
4,497
kWh
|
- | |
07 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $467 | $200 | - |
$467
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $17,092 | $17,434 |
$14,230
113,383
kWh
|
$2,862
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $2,768 | $2,210 |
$2,768
22,049
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs