Assessment Year | 2012 |
---|---|
Principal Product | candy |
NAICS | 445292: Confectionery and Nut Stores |
SIC | 5441: Candy, Nut, and Confectionery Stores |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
165,000
ft2
|
Annual Production | 12,000,000
lb
|
Production Hrs. Annual | 4,550
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $328,364 | 3,834,874 |
kWh
|
$0.086 |
Electricity Demand | $153,716 | 32,720 |
kW-mo/yr
|
$4.70 |
Electricity Fees | $71,049 | - |
|
- |
Natural Gas | $112,765 | 16,215 |
MMBtu
|
$6.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $20,213 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,941 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,392 | $100 |
$4,392
51,310
kWh
|
- | - | - | |
02 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $3,454 | $100 |
$3,017
35,247
kWh
|
$437
-
kW-mo/yr
|
- | - | |
03 | 2.2135: Repair and eliminate steam leaks | $1,042 | $200 | - | - | - |
$1,042
-
MMBtu
|
|
04 | 2.2135: Repair and eliminate steam leaks | $4,456 | $1,200 |
$3,892
45,467
kWh
|
$564
-
kW-mo/yr
|
- | - | |
05 | 2.7135: Install occupancy sensors | $1,629 | $2,471 |
$1,629
19,035
kWh
|
- | - | - | |
06 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $865 | $1,500 |
$1,052
12,285
kWh
|
$178
-
kW-mo/yr
|
- |
$(-364.4)
-
MMBtu
|
|
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,186 | $2,022 |
$1,036
12,103
kWh
|
$150
-
kW-mo/yr
|
- | - | |
08 | 2.3212: Optimize plant power factor | $3,189 | $5,775 | - | - | $3,189 | - | |
TOTAL RECOMMENDED | $20,213 | $13,368 |
$15,018
175,447
kWh
|
$1,329
-
kW-mo/yr
|
$3,189 |
$678
-
MMBtu
|
||
TOTAL IMPLEMENTED | $11,941 | $5,022 |
$10,372
121,165
kWh
|
$892
-
kW-mo/yr
|
- |
$678
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs