| Assessment Year | 2010 |
|---|---|
| Principal Product | Waste water, Reclaimed water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 3589: Service Industry Machinery, Not Elsewhere Classified |
| Sales Range | less than $500 k |
| # of Employees | 19 |
| Plant Area |
10,000
ft2
|
| Annual Production | 4,380,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $637,470 | 7,586,488 |
kWh
|
$0.084 |
| Electricity Demand | $322,754 | 19,568 |
kW-mo/yr
|
$16.49 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $51,455 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $42,981 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,908 | $100 |
$3,908
46,518
kWh
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,098 | $100 |
$1,098
13,069
kWh
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,468 | $1,000 |
$3,468
41,280
kWh
|
- | |
| 04 | 2.7135: Install occupancy sensors | $496 | $1,334 |
$496
5,906
kWh
|
- | |
| 05 | 2.7232: Replace existing hvac unit with high efficiency model | $42,485 | $260,000 |
$33,480
398,580
kWh
|
$9,005
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $51,455 | $262,534 |
$42,450
505,353
kWh
|
$9,005
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $42,981 | $261,334 |
$33,976
404,486
kWh
|
$9,005
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs