Assessment Year 2009
Principal Product Cookies and Crakers
NAICS 311821: Cookie and Cracker Manufacturing
SIC 2052: Cookies and Crackers
Sales Range $100
M
to 500
M
# of Employees 325
Plant Area 88,000
ft2
Annual Production 1
units
Production Hrs. Annual 7,200
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $219,953 2,582,822
kWh
Electricity Demand $90,104 5,537
kW-mo/yr
Electricity Fees $31,496 -
Natural Gas $159,933 23,792
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $254,741 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Fuel Oil #1 Savings Other Energy Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $1,697 - $1,697
19,920
kWh
- - -
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $995 $130 $755
8,862
kWh
$240
-
kW-mo/yr
- -
03 2.2614: Use cooling tower or economizer to replace chiller cooling $19,013 $4,062 $14,590
171,289
kWh
$4,423
-
kW-mo/yr
- -
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,335 $300 $1,335
15,666
kWh
- - -
05 2.4239: Eliminate or reduce compressed air usage $6,107 $5,200 $4,643
54,502
kWh
$1,464
-
kW-mo/yr
- -
06 2.7425: Clean or color roof to reduce solar load $7,887 $14,667 $7,887
92,571
kWh
- - -
07 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat $217,707 $718,800 $301,812
3,542,400
kWh
$96,058
-
kW-mo/yr
$(-234,256.0)
-
MMBtu
$54,093
-
MMBtu
TOTAL RECOMMENDED $254,741 $743,159 $332,719
3,905,210
kWh
$102,185
-
kW-mo/yr
$(-234,256.0)
-
MMBtu
$54,093
-
MMBtu
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Fuel Oil #1 Savings Other Energy Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs