| Assessment Year | 2009 |
|---|---|
| Principal Product | Roasting and seasoning nuts and seeds |
| NAICS | 311911: Roasted Nuts and Peanut Butter Manufacturing |
| SIC | 2099: Food Preparations, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 135 |
| Plant Area |
69,000
ft2
|
| Annual Production | 350
pieces
|
| Production Hrs. Annual | 4,335
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $59,327 | 552,120 |
kWh
|
$0.11 |
| Electricity Demand | $19,410 | 1,953 |
kW-mo/yr
|
$9.94 |
| Electricity Fees | $3,281 | - |
|
- |
| Natural Gas | $35,800 | 30,276 |
MMBtu
|
$1.18 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $45,210 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $16,624 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,133 | $35,628 |
$7,133
51,683
kWh
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,893 | $5,295 |
$4,893
35,679
kWh
|
|
| 03 | 2.7134: Use photocell controls | $3,458 | $4,950 |
$3,458
32,026
kWh
|
|
| 04 | 2.7425: Clean or color roof to reduce solar load | $28,586 | $26,000 |
$28,586
225,789
kWh
|
|
| 05 | 2.7232: Replace existing hvac unit with high efficiency model | $655 | - |
$655
4,590
kWh
|
|
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $485 | - |
$485
4,517
kWh
|
|
| TOTAL RECOMMENDED | $45,210 | $71,873 |
$45,210
354,284
kWh
|
||
| TOTAL IMPLEMENTED | $16,624 | $45,873 |
$16,624
128,495
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs