| Assessment Year | 2006 |
|---|---|
| Principal Product | Tomato Paste |
| NAICS | 311421: Fruit and Vegetable Canning |
| SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
| Sales Range | $5 M to 10M |
| # of Employees | 150 |
| Plant Area |
200,000
ft2
|
| Annual Production | 7,000,000
lb
|
| Production Hrs. Annual | 5,124
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $671,077 | 9,065,393 |
kWh
|
$0.074 |
| Electricity Demand | $204,564 | 22,980 |
kW-mo/yr
|
$8.90 |
| Natural Gas | $6,603,311 | 931,213 |
MMBtu
|
$7.09 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $233,444 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,543 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $231,300 | $1,500,000 |
$202,331
2,734,200
kWh
|
$28,969
-
kW-mo/yr
|
- | |
| 02 | 2.7134: Use photocell controls | $846 | $480 |
$392
5,304
kWh
|
$454
-
kW-mo/yr
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $433 | $2,797 |
$273
3,686
kWh
|
$160
-
kW-mo/yr
|
- | |
| 04 | 2.2414: Use waste heat from hot flue gases to preheat | $601 | $4,125 | - | - |
$601
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $264 | $1,006 |
$167
2,257
kWh
|
$97
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $233,444 | $1,508,408 |
$203,163
2,745,447
kWh
|
$29,680
-
kW-mo/yr
|
$601
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $1,543 | $4,283 |
$832
11,247
kWh
|
$711
-
kW-mo/yr
|
- | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs