Assessment Year | 2005 |
---|---|
Principal Product | corrugated boxes and containers |
NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
125,000
ft2
|
Annual Production | 30,000,000
pieces
|
Production Hrs. Annual | 4,335
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $176,184 | 1,996,579 |
kWh
|
$0.088 |
Electricity Demand | $85,757 | 8,236 |
kW-mo/yr
|
$10.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $46,467 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,734 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $5,391 | $11,000 |
$5,391
61,121
kWh
|
- | - | - | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,992 | $14,000 |
$4,992
56,593
kWh
|
- | - | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,583 | $7,647 |
$2,698
30,656
kWh
|
$885
-
kW-mo/yr
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,351 | $120 |
$1,771
20,082
kWh
|
$580
-
kW-mo/yr
|
- | - | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,151 | - |
$1,151
13,046
kWh
|
- | - | - | - | |
06 | 3.3131: Use evaporation to concentrate material | $18,769 | $25,650 |
$2,138
24,245
kWh
|
$700
-
kW-mo/yr
|
$(-8,069.0)
-
MMBtu
|
$24,000
-
gal
|
- | |
07 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $10,230 | $18,500 | - | - | - | - |
$10,230
-
lb
|
|
TOTAL RECOMMENDED | $46,467 | $76,917 |
$18,141
205,743
kWh
|
$2,165
-
kW-mo/yr
|
$(-8,069.0)
-
MMBtu
|
$24,000
-
gal
|
$10,230
-
lb
|
||
TOTAL IMPLEMENTED | $12,734 | $25,120 |
$12,154
137,796
kWh
|
$580
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs