Assessment Year | 2003 |
---|---|
Principal Product | Medical Products |
NAICS | 339112: Surgical and Medical Instrument Manufacturing |
SIC | 3841: Surgical and Medical Instruments and Apparatus |
Sales Range | n/a |
# of Employees | 450 |
Plant Area |
50,000
ft2
|
Annual Production | 92,800
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Demand | $1,410,834 | 13,526,680 |
kW-mo/yr
|
$0.10 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $319,789 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $199,630 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $88,041 | $300,075 |
$83,053
796,289
kWh
|
$4,988
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $71,754 | - |
$67,376
645,987
kWh
|
$4,378
-
kW-mo/yr
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $53,956 | $32,725 |
$48,199
462,116
kWh
|
$5,757
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $37,849 | $2,000 |
$35,836
343,540
kWh
|
$2,013
-
kW-mo/yr
|
|
05 | 2.7261: Install timers and/or thermostats | $36,071 | $1,000 |
$36,071
345,840
kWh
|
- | |
06 | 2.2625: Chill water to the highest temperature possible | $14,542 | - |
$4,988
47,826
kWh
|
$9,554
-
kW-mo/yr
|
|
07 | 2.7145: Install skylights | $9,297 | $18,000 |
$4,756
45,600
kWh
|
$4,541
-
kW-mo/yr
|
|
08 | 2.4239: Eliminate or reduce compressed air usage | $8,279 | $1,410 |
$8,279
79,381
kWh
|
- | |
TOTAL RECOMMENDED | $319,789 | $355,210 |
$288,558
2,766,579
kWh
|
$31,231
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $199,630 | $35,725 |
$187,482
1,797,483
kWh
|
$12,148
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs