Assessment Year 2001
Principal Product Brass mill rod and shape products
NAICS
n/a
SIC 3351: Rolling, Drawing, and Extruding Of Copper
Sales Range $10
M
to 50
M
# of Employees 130
Plant Area 320,000
ft2
Annual Production 40,000,000
lb
Production Hrs. Annual 6,000
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $720,008 15,981,904
kWh
Electricity Demand $31,122 41,786
kW-mo/yr
Electricity Fees $28,175 -
Natural Gas $169,721 33,995
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $591,362 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $34,478

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Solid Waste (haz) Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $34,478 $1,400 $33,380
741,762
kWh
$1,098
-
kW-mo/yr
- - - - -
02 2.4321: Upgrade obsolete equipment $32,897 $60,000 $32,002
709,578
kWh
$895
-
kW-mo/yr
- - - - -
03 2.7145: Install skylights $17,602 $37,000 $15,560
345,000
kWh
$2,042
-
kW-mo/yr
- - - - -
04 2.4322: Use or replace with energy efficient substitutes $1,025 $2,250 $972
21,560
kWh
$53
-
kW-mo/yr
- - - - -
05 2.1311: Replace electrically-operated equipment with fossil fuel equipment $21,557 $45,000 $32,472
720,000
kWh
$1,776
-
kW-mo/yr
$(-12,691.0)
-
MMBtu
- - - -
06 2.4321: Upgrade obsolete equipment $465,613 $1,000,000 $39,293
871,250
kWh
$1,820
-
kW-mo/yr
- $48,000
-
gal
- $376,500 -
07 3.6193: Install equipment (eg compactor) to reduce disposal costs $4,190 $15,000 - - - - - - $4,190
08 3.7198: Reduce / eliminate use of disposable product $14,000 $5,800 - - - - $14,000
-
lb
- -
TOTAL RECOMMENDED $591,362 $1,166,450 $153,679
3,409,150
kWh
$7,684
-
kW-mo/yr
$(-12,691.0)
-
MMBtu
$48,000
-
gal
$14,000
-
lb
$376,500 $4,190
TOTAL IMPLEMENTED $34,478 $1,400 $33,380
741,762
kWh
$1,098
-
kW-mo/yr
- - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Solid Waste (haz) Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs