Assessment Year | 1998 |
---|---|
Principal Product | Metallic and Non-Metallic Ducting |
NAICS |
n/a
|
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $50 M to 100M |
# of Employees | 450 |
Plant Area |
250,000
ft2
|
Annual Production | 240,000
pieces
|
Production Hrs. Annual | 4,890
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $234,077 | 4,300,997 |
kWh
|
$0.054 |
Electricity Demand | $186,069 | 18,212 |
kW-mo/yr
|
$10.22 |
Natural Gas | $55,736 | 10,093 |
MMBtu
|
$5.52 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $151,891 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,042 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $4,838 | $5,890 |
$3,277
60,668
kWh
|
$1,561
-
kW-mo/yr
|
- | - | - | - | - | |
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $45,498 | $34,650 |
$32,621
604,338
kWh
|
$12,877
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,897 | $1,800 |
$7,862
145,369
kWh
|
$3,035
-
kW-mo/yr
|
- | - | - | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,084 | $41,850 |
$6,461
119,578
kWh
|
$3,623
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.2515: Use optimum thickness insulation | $3,919 | $5,418 | - | - |
$3,919
-
MMBtu
|
- | - | - | - | |
06 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $18,900 | $8,500 | - | - | - | - | - | - | $18,900 | |
07 | 3.8224: Convert to less toxic hydrocarbon cleaners | $15,696 | $1,450 | - | - | - | - |
$15,696
-
gal
|
- | - | |
08 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $12,650 | - | - | - | - | - | - |
$12,650
-
lb
|
- | |
09 | 3.4113: Treat and reuse rinse waters | $654 | $750 | - | - | - |
$654
-
gal
|
- | - | - | |
10 | 4.112: Replace old machine with new automatic multi-station tool | $28,755 | $200,000 | - | - | - | - | - | - | $28,755 | |
TOTAL RECOMMENDED | $151,891 | $300,308 |
$50,221
929,953
kWh
|
$21,096
-
kW-mo/yr
|
$3,919
-
MMBtu
|
$654
-
gal
|
$15,696
-
gal
|
$12,650
-
lb
|
$47,655 | ||
TOTAL IMPLEMENTED | $37,042 | $15,140 |
$3,277
60,668
kWh
|
$1,561
-
kW-mo/yr
|
- |
$654
-
gal
|
- |
$12,650
-
lb
|
$18,900 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs