Assessment Year | 1997 |
---|---|
Principal Product | Plastic bags, shipping sacks, shipping envelopes and polyeth |
NAICS |
n/a
|
SIC | 2673: Plastics, Foil, and Coated Paper Bags |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
37,000
ft2
|
Annual Production | 14,000,000
lb
|
Production Hrs. Annual | 8,640
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $341,244 | 6,851,114 |
kWh
|
$0.050 |
Electricity Demand | $192,003 | 11,563 |
kW-mo/yr
|
$16.60 |
Natural Gas | $7,412 | 1,184 |
MMBtu
|
$6.26 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $172,586 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $120,732 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $23,299 | $26,840 |
$15,946
318,875
kWh
|
$7,353
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,867 | $400 |
$1,962
39,273
kWh
|
$905
-
kW-mo/yr
|
- | - | - | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $51,854 | $28,000 |
$39,600
792,204
kWh
|
$16,434
-
kW-mo/yr
|
$(-4,180.0)
-
MMBtu
|
- | - | |
04 | 3.3128: Utilize other methods to remove contaminants | $3,600 | $7,000 | - | - | - | - | $3,600 | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $22,009 | $19,050 |
$16,436
241,794
kWh
|
$5,573
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,642 | $1,989 |
$3,162
63,306
kWh
|
$1,480
-
kW-mo/yr
|
- | - | - | |
07 | 2.7144: Install spectral reflectors / delamp | $618 | $960 |
$317
6,448
kWh
|
$301
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $1,790 | $369 |
$1,115
22,274
kWh
|
$675
-
kW-mo/yr
|
- | - | - | |
09 | 3.5311: Recover and reuse waste material | $15,300 | $5,500 | - | - | - | - | $15,300 | |
10 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $5,900 | $9,000 | - | - | - | - | $5,900 | |
11 | 3.7134: Wash and reuse rags on-site | $2,920 | $500 | - | - | - |
$2,920
-
lb
|
- | |
12 | 4.821: Pay bills on time to avoid late fees | $3,467 | - | - | - | - | - | $3,467 | |
13 | 4.441: Install automatic packing equipment | $34,320 | $350 | - | - | - | - | $34,320 | |
TOTAL RECOMMENDED | $172,586 | $99,958 |
$78,538
1,484,174
kWh
|
$32,721
-
kW-mo/yr
|
$(-4,180.0)
-
MMBtu
|
$2,920
-
lb
|
$62,587 | ||
TOTAL IMPLEMENTED | $120,732 | $71,958 |
$38,938
691,970
kWh
|
$16,287
-
kW-mo/yr
|
- |
$2,920
-
lb
|
$62,587 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs