Assessment Year | 1996 |
---|---|
Principal Product | Printed Circuit Boards |
NAICS |
n/a
|
SIC | 3571: Electronic Computers |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
97,000
ft2
|
Annual Production | 40,000
pieces
|
Production Hrs. Annual | 4,125
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $160,889 | 3,162,661 |
kWh
|
$0.051 |
Electricity Demand | $103,039 | 6,156 |
kW-mo/yr
|
$16.74 |
Electricity Fees | $4,443 | - |
|
- |
Natural Gas | $21,358 | 3,012 |
MMBtu
|
$7.09 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $47,690 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $2,319 | $3,090 |
$2,319
15,826
kWh
|
- | - | |
02 | 2.7229: Air condition only space necessary | $20,835 | - |
$20,835
239,449
kWh
|
- | - | |
03 | 2.3212: Optimize plant power factor | $3,817 | $1,616 | - | $3,817 | - | |
04 | 2.2511: Insulate bare equipment | $358 | $114 |
$358
2,931
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,748 | $19,039 |
$7,748
70,047
kWh
|
- | - | |
06 | 2.7144: Install spectral reflectors / delamp | $8,071 | $11,310 |
$8,071
72,978
kWh
|
- | - | |
07 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $3,980 | $9,000 | - | - |
$3,980
-
lb
|
|
08 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $562 | - | - | - |
$562
-
lb
|
|
TOTAL RECOMMENDED | $47,690 | $44,169 |
$39,331
401,231
kWh
|
$3,817 |
$4,542
-
lb
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs