| Assessment Year | 1996 |
|---|---|
| Principal Product | Pyrogenic External Torches |
| NAICS |
n/a
|
| SIC | 3821: Laboratory Apparatus and Furniture |
| Sales Range | $5 M to 10M |
| # of Employees | 188 |
| Plant Area |
76,500
ft2
|
| Annual Production | 350
units
|
| Production Hrs. Annual | 4,992
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $139,699 | 1,774,912 |
kWh
|
$0.079 |
| Electricity Demand | $28,605 | 3,897 |
kW-mo/yr
|
$7.34 |
| Natural Gas | $72,756 | 11,787 |
MMBtu
|
$6.17 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $75,801 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $75,801 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $2,889 | $3,260 |
$2,889
28,722
kWh
|
- | - | |
| 02 | 2.2442: Preheat combustion air with waste heat | $2,074 | $2,083 | - |
$2,074
-
MMBtu
|
- | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,321 | $40 |
$1,321
13,775
kWh
|
- | - | |
| 04 | 2.2515: Use optimum thickness insulation | $1,905 | $651 |
$1,905
89,977
kWh
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,979 | $5,928 |
$3,979
41,618
kWh
|
- | - | |
| 06 | 2.7144: Install spectral reflectors / delamp | $6,002 | $4,080 |
$6,002
62,720
kWh
|
- | - | |
| 07 | 2.7135: Install occupancy sensors | $1,471 | $1,001 |
$1,471
15,240
kWh
|
- | - | |
| 08 | 3.1192: Reduce scrap production | $56,160 | - | - | - |
$56,160
-
lb
|
|
| TOTAL RECOMMENDED | $75,801 | $17,043 |
$17,567
252,052
kWh
|
$2,074
-
MMBtu
|
$56,160
-
lb
|
||
| TOTAL IMPLEMENTED | $75,801 | $17,043 |
$17,567
252,052
kWh
|
$2,074
-
MMBtu
|
$56,160
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs