Assessment Year | 1992 |
---|---|
Principal Product | POWER CONDITIONERS |
NAICS |
n/a
|
SIC | 3629: Electrical Industrial Apparatus, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
n/a
|
Annual Production | 6,000
pieces
|
Production Hrs. Annual | 2,125
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $90,415 | 927,022 |
kWh
|
$0.098 |
Natural Gas | $384 | 49 |
MMBtu
|
$7.84 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,870 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,860 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $92 | $233 |
$92
879
kWh
|
- | |
02 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $870 | $620 |
$870
8,792
kWh
|
- | |
03 | 2.2531: Re-size charging openings or add movable cover or door | $1,562 | $120 |
$1,562
16,120
kWh
|
- | |
04 | 2.2437: Recover waste heat from equipment | $1,764 | $551 |
$1,764
17,878
kWh
|
- | |
05 | 2.2437: Recover waste heat from equipment | $635 | $729 |
$635
6,448
kWh
|
- | |
06 | 2.6224: Schedule baking times of small and large components | $417 | - |
$417
4,396
kWh
|
- | |
07 | 2.6232: Install set-back timers | $3,338 | $7,500 |
$3,338
31,360
kWh
|
- | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $1,830 | $600 |
$1,830
18,757
kWh
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,375 | $3,300 |
$2,375
24,033
kWh
|
- | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $593 | - |
$808
8,206
kWh
|
$(-215.0) | |
11 | 2.7123: Keep lamps and reflectors clean | $4,343 | $10,788 |
$4,343
42,204
kWh
|
- | |
12 | 2.7226: Use computer programs to optimize hvac performance | $14,051 | $2,500 |
$14,051
143,904
kWh
|
- | |
TOTAL RECOMMENDED | $31,870 | $26,941 |
$32,085
322,977
kWh
|
$(-215.0) | ||
TOTAL IMPLEMENTED | $28,860 | $22,912 |
$29,075
292,496
kWh
|
$(-215.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs