Assessment Year | 1992 |
---|---|
Principal Product | TRANSPORTATION EQUIPMENT |
NAICS |
n/a
|
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 82 |
Plant Area |
n/a
|
Annual Production | 550
pieces
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $143,105 | 1,555,686 |
kWh
|
$0.092 |
Natural Gas | $10,384 | 1,623 |
MMBtu
|
$6.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $23,749 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $564 | $423 |
$564
6,155
kWh
|
- | - | |
02 | 2.6218: Turn off equipment when not in use | $5,920 | $505 |
$(-224.0)
(-2,345)
kWh
|
$6,144
-
MMBtu
|
- | |
03 | 2.4322: Use or replace with energy efficient substitutes | $3,341 | $3,300 | - |
$3,341
-
MMBtu
|
- | |
04 | 2.2531: Re-size charging openings or add movable cover or door | $459 | $109 |
$459
4,982
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,115 | $448 |
$883
9,672
kWh
|
- | $232 | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $12,350 | $30,068 |
$11,145
123,681
kWh
|
- | $1,205 | |
TOTAL RECOMMENDED | $23,749 | $34,853 |
$12,827
142,145
kWh
|
$9,485
-
MMBtu
|
$1,437 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs