| Assessment Year | 2026 |
|---|---|
| Principal Product | none |
| NAICS | 611110: Elementary and Secondary Schools |
| SIC | 8211: Elementary and Secondary Schools |
| Sales Range | less than $500 k |
| # of Employees | 25 |
| Plant Area |
80,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $29,441 | 312,840 |
kWh
|
$0.094 | |
| Electricity Demand | $12,709 | 609 |
kW-mo/yr
|
$20.87 | |
| Electricity Fees | $10,910 | - |
|
- | |
| Natural Gas | $24,373 | 1,899 |
MMBtu
|
$12.83 | |
| Waste Disposal Costs | |||||
| Water Usage | $5,000 | 1,000 |
Tgal
|
$5.00 | |
| TOTAL YEARLY COSTS | $82,433 | ||||
| RECOMMENDED SAVINGS* | $28,840 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $1,315 | - |
$1,315
13,975
kWh
|
- | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $112 | $25 |
$112
1,188
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,134 | $8,101 |
$5,891
62,600
kWh
|
$5,243
-
kW-mo/yr
|
|
| 04 | 2.7226: Use computer programs to optimize hvac performance | $1,254 | $1,732 |
$961
10,216
kWh
|
$293
-
kW-mo/yr
|
|
| 05 | 2.7229: Air condition only space necessary | $591 | $1,000 |
$591
6,285
kWh
|
- | |
| 06 | 2.9114: Use solar heat to make electricty | $14,434 | $204,700 |
$10,302
109,472
kWh
|
$4,132
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $28,840 | $215,558 |
$19,172
203,736
kWh
|
$9,668
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs