Assessment Year | 2023 |
---|---|
Principal Product | Support Sercices |
NAICS | 611210: Junior Colleges |
SIC | 8222: Junior Colleges and Technical Institutes |
Sales Range | less than $500 k |
# of Employees | 100 |
Plant Area |
100,000
ft2
|
Annual Production | 100
pieces
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $44,784 | 1,417,200 |
kWh
|
$0.032 | |
Electricity Demand | $5,606 | 4,115 |
kW-mo/yr
|
$1.36 | |
Electricity Fees | $26,227 | - |
|
- | |
Natural Gas | $18,063 | 2,195 |
MMBtu
|
$8.23 | |
Waste Disposal Costs | |||||
Water Usage | $8,209 | 459 |
Tgal
|
$17.88 | |
TOTAL YEARLY COSTS | $102,889 | ||||
RECOMMENDED SAVINGS* | $11,586 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $1,964 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,080 | $12,000 |
$1,066
33,732
kWh
|
$14
-
kW-mo/yr
|
- | - | |
02 | 2.7314: Reduce ventilation air | $8,470 | $1,000 |
$1,664
52,671
kWh
|
- |
$6,806
-
MMBtu
|
- | |
03 | 2.2515: Use optimum thickness insulation | $72 | $100 |
$72
2,287
kWh
|
- | - | - | |
04 | 3.4151: Minimize water usage | $1,964 | $8,000 | - | - | - |
$1,964
-
Tgal
|
|
TOTAL RECOMMENDED | $11,586 | $21,100 |
$2,802
88,690
kWh
|
$14
-
kW-mo/yr
|
$6,806
-
MMBtu
|
$1,964
-
Tgal
|
||
TOTAL IMPLEMENTED | $1,964 | $8,000 | - | - | - |
$1,964
-
Tgal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs