| Assessment Year | 2026 |
|---|---|
| Principal Product | Diamond speaker domes, CVD diamond optical components, chemical vapor deposition diamond heat spreaders, PCD and PCBN discs, polycrystalline diamond compact cutters |
| NAICS | 327999: All Other Miscellaneous Nonmetallic Mineral Product Manufacturing |
| SIC | 3299: Nonmetallic Mineral Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 80 |
| Plant Area |
50,000
ft2
|
| Annual Production | 10,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,212,597 | 17,746,731 |
kWh
|
$0.068 | |
| Electricity Demand | $624,704 | 33,394 |
kW-mo/yr
|
$18.71 | |
| Fuel Oil #2 | $3,000 | 90 |
MMBtu
|
$33.33 | |
| Waste Disposal Costs | |||||
| Water Usage | $35,313 | 6,481 |
Tgal
|
$5.45 | |
| Other Liquid (haz) | $11,176 | 12,003 |
gal
|
$0.93 | |
| TOTAL YEARLY COSTS | $1,886,790 | ||||
| RECOMMENDED SAVINGS* | $170,473 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Water Usage Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Increase in Production Savings |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $36,378 | - |
$36,378
532,402
kWh
|
- | - | - | - | - | - | |
| 02 | 2.4322: Use or replace with energy efficient substitutes | $1,500 | - | - | - |
$1,500
-
MMBtu
|
- | - | - | - | |
| 03 | 3.4156: Use flow control valves on equipment to optimize water use | $79,017 | $25,616 |
$39,045
571,431
kWh
|
$14,972
-
kW-mo/yr
|
- | - | - | - | $25,000 | |
| 04 | 3.4159: Replace treated water with well / surface water | $8,249 | $6,786 | - | - | - |
$8,249
-
Tgal
|
- | - | - | |
| 05 | 2.6127: Maintain air filters by cleaning or replacement | $8,393 | $10,000 |
$(-715.0)
(-10,470)
kWh
|
- | - |
$(-251.0)
-
Tgal
|
- | $9,359 | - | |
| 06 | 4.212: Adopt in-house material generation | $6,766 | $68,142 |
$(-3,190.0)
(-46,683)
kWh
|
$(-1,220.0)
-
kW-mo/yr
|
- | - |
$11,176
-
gal
|
- | - | |
| 07 | 2.9114: Use solar heat to make electricty | $30,170 | $735,960 |
$24,494
358,466
kWh
|
$5,676
-
kW-mo/yr
|
- | - | - | - | - | |
| TOTAL RECOMMENDED | $170,473 | $846,504 |
$96,012
1,405,146
kWh
|
$19,428
-
kW-mo/yr
|
$1,500
-
MMBtu
|
$7,998
-
Tgal
|
$11,176
-
gal
|
$9,359 | $25,000 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Water Usage Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Increase in Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs