| Assessment Year | 2025 |
|---|---|
| Principal Product | Windows |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3442: Metal Doors, Sash, Frames, Molding, and Trim Manufacturing |
| Sales Range | $50 M to 100M |
| # of Employees | 240 |
| Plant Area |
327,000
ft2
|
| Annual Production | 450,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $840,359 | 9,825,114 |
kWh
|
$0.086 |
| Electricity Demand | $219,277 | 18,706 |
kW-mo/yr
|
$11.72 |
| Natural Gas | $27,372 | 2,078 |
MMBtu
|
$13.17 |
| TOTAL YEARLY COSTS | $1,087,008 | |||
| RECOMMENDED SAVINGS* | $59,541 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,865 | - |
$8,412
98,357
kWh
|
$1,579
-
kW-mo/yr
|
$9,874 | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $14,423 | - |
$14,423
168,630
kWh
|
- | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,774 | $3,661 |
$9,913
115,906
kWh
|
$1,861
-
kW-mo/yr
|
- | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $10,035 | $1,456 |
$8,449
98,787
kWh
|
$1,586
-
kW-mo/yr
|
- | |
| 05 | 2.7132: Install timers on light switches in little used areas | $3,444 | $16,650 |
$3,444
40,270
kWh
|
- | - | |
| TOTAL RECOMMENDED | $59,541 | $21,767 |
$44,641
521,950
kWh
|
$5,026
-
kW-mo/yr
|
$9,874 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs