| Assessment Year | 2016 |
|---|---|
| Principal Product | Finished Metals |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $10 M to 50M |
| # of Employees | 81 |
| Plant Area |
35,000
ft2
|
| Annual Production | 15,000,000
units
|
| Production Hrs. Annual | 4,680
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $90,143 | 1,453,360 |
kWh
|
$0.062 |
| Electricity Demand | $23,121 | 4,070 |
kW-mo/yr
|
$5.68 |
| Electricity Fees | $9,804 | - |
|
- |
| Natural Gas | $69,757 | 12,368 |
MMBtu
|
$5.64 |
| TOTAL YEARLY COSTS | $192,825 | |||
| RECOMMENDED SAVINGS* | $27,212 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $9,436 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.2511: Insulate bare equipment | $7,372 | $5,408 | - | - |
$7,372
-
MMBtu
|
- | - | |
| 02 | 2.2211: Use optimum temperature | $1,822 | $300 | - | - |
$5,844
-
MMBtu
|
$(-4,022.0) | - | |
| 03 | 2.1224: Replace boiler | $4,164 | $17,322 | - | - |
$4,164
-
MMBtu
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,583 | $22,256 |
$9,120
141,622
kWh
|
$1,531
-
kW-mo/yr
|
- | $507 | $(-575.0) | |
| 05 | 2.2511: Insulate bare equipment | $2,064 | $658 | - | - |
$2,064
-
MMBtu
|
- | - | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,207 | $944 |
$863
13,373
kWh
|
$344
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $27,212 | $46,888 |
$9,983
154,995
kWh
|
$1,875
-
kW-mo/yr
|
$19,444
-
MMBtu
|
$(-3,515.0) | $(-575.0) | ||
| TOTAL IMPLEMENTED | $9,436 | $6,066 | - | - |
$9,436
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs