Assessment Year | 2014 |
---|---|
Principal Product | Cases Distributed Annually |
NAICS | 312111: Soft Drink Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
305,000
ft2
|
Annual Production | 22,672,500
pieces
|
Production Hrs. Annual | 5,800
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $614,317 | 10,701,440 |
kWh
|
$0.057 |
Electricity Demand | $309,381 | 27,284 |
kW-mo/yr
|
$11.34 |
Electricity Fees | $65,746 | - |
|
- |
Natural Gas | $457,972 | 64,237 |
MMBtu
|
$7.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,895 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,727 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $11,360 | $250 |
$11,360
190,348
kWh
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,168 | $5,544 |
$4,818
80,736
kWh
|
$1,350
-
kW-mo/yr
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $1,567 | $1,634 |
$1,292
21,641
kWh
|
$547
-
kW-mo/yr
|
- | $(-272.0) | |
04 | 2.2136: Install / repair insulation on steam lines | $800 | $417 | - | - |
$800
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $19,895 | $7,845 |
$17,470
292,725
kWh
|
$1,897
-
kW-mo/yr
|
$800
-
MMBtu
|
$(-272.0) | ||
TOTAL IMPLEMENTED | $13,727 | $2,301 |
$12,652
211,989
kWh
|
$547
-
kW-mo/yr
|
$800
-
MMBtu
|
$(-272.0) |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs