Assessment Year | 2014 |
---|---|
Principal Product | Woolen Textiles |
NAICS | 313210: Broadwoven Fabric Mills |
SIC | 2231: Broadwoven Fabric Mills, Wool (Including Dyeing and Finishing) |
Sales Range | $10 M to 50M |
# of Employees | 290 |
Plant Area |
300,000
ft2
|
Annual Production | 1,500,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $387,449 | 8,282,700 |
kWh
|
$0.047 |
Electricity Demand | $128,747 | 21,534 |
kW-mo/yr
|
$5.98 |
Electricity Fees | $33,516 | - |
|
- |
Natural Gas | $448,594 | 84,908 |
MMBtu
|
$5.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,571 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,127 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $8,251 | $22,500 |
$6,688
135,818
kWh
|
$1,563
-
kW-mo/yr
|
- | - | - | |
02 | 2.6242: Minimize operation of equipment maintained in standby condition | $2,193 | $468 |
$2,193
44,534
kWh
|
- | - | - | - | |
03 | 2.2121: Increase amount of condensate returned | $12,766 | $6,839 | - | - |
$12,766
-
MMBtu
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,361 | $30,178 |
$2,436
49,473
kWh
|
$919
-
kW-mo/yr
|
- | $146 | $860 | |
TOTAL RECOMMENDED | $27,571 | $59,985 |
$11,317
229,825
kWh
|
$2,482
-
kW-mo/yr
|
$12,766
-
MMBtu
|
$146 | $860 | ||
TOTAL IMPLEMENTED | $17,127 | $37,017 |
$2,436
49,473
kWh
|
$919
-
kW-mo/yr
|
$12,766
-
MMBtu
|
$146 | $860 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs