| Assessment Year | 2006 |
|---|---|
| Principal Product | Dimensional Lumber |
| NAICS | 321113: Sawmills |
| SIC | 2421: Sawmills and Planing Mills, General |
| Sales Range | $10 M to 50M |
| # of Employees | 145 |
| Plant Area |
1,742,400
ft2
|
| Annual Production | 55,000,000
units
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $275,000 | 8,001,748 |
kWh
|
$0.034 |
| Electricity Demand | $123,180 | 27,323 |
kW-mo/yr
|
$4.51 |
| Electricity Fees | $15 | - |
|
- |
| Natural Gas | $201,943 | 235,083 |
MMBtu
|
$0.86 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $5,109,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $57,180 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Increase in Production Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 4.453: Reschedule breaks to allow for continuous production | $5,052,000 | - | - | - | - | $5,052,000 | |
| 02 | 2.4112: Install soft-start to eliminate nuisance trips | $5,700 | - |
$5,700
160,000
kWh
|
- | - | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,300 | $6,300 |
$5,100
143,000
kWh
|
$1,200
-
kW-mo/yr
|
- | - | |
| 04 | 2.4224: Upgrade controls on compressors | $18,300 | $27,500 |
$16,000
447
kWh
|
$2,300
-
kW-mo/yr
|
- | - | |
| 05 | 2.3212: Optimize plant power factor | $12,600 | $48,600 | - | - | $12,600 | - | |
| 06 | 2.4133: Use most efficient type of electric motors | $14,280 | $72,900 |
$10,300
288,290
kWh
|
$3,980
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $5,109,180 | $155,300 |
$37,100
591,737
kWh
|
$7,480
-
kW-mo/yr
|
$12,600 | $5,052,000 | ||
| TOTAL IMPLEMENTED | $57,180 | $155,300 |
$37,100
591,737
kWh
|
$7,480
-
kW-mo/yr
|
$12,600 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Increase in Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs