Assessment Year | 2003 |
---|---|
Principal Product | Asphalt, Aggregate, STB |
NAICS | 212321: Construction Sand and Gravel Mining |
SIC | 1442: Construction Sand and Gravel |
Sales Range | $10 M to 50M |
# of Employees | 14 |
Plant Area |
n/a
|
Annual Production | 825,000
ton
|
Production Hrs. Annual | 535
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $153,182 | 3,238,200 |
kWh
|
$0.047 |
Electricity Demand | $91,536 | 21,192 |
kW-mo/yr
|
$4.32 |
Electricity Fees | $18,800 | - |
|
- |
Fuel Oil #2 | $167,283 | 40,136 |
MMBtu
|
$4.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $139,493 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,638 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 4.321: Optimize production lot sizes and inventories | $123,700 | $303,000 | n/a | - | - | - | - | $37,200 | - | $86,500 |
02 | 2.4133: Use most efficient type of electric motors | $4,860 | $5,450 |
$2,800
57,200
kWh
|
$2,060
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 2.1113: Reduce combustion air flow to optimum | $1,778 | $150 | - | - | - |
$2,078
-
MMBtu
|
- | $(-300.0) | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,960 | - |
$1,240
25,300
kWh
|
$720
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,505 | - | - |
$864
-
kW-mo/yr
|
$641 | - | - | - | - | |
06 | 2.3212: Optimize plant power factor | $5,690 | $20,000 | - | - | $5,690 | - | - | - | - | |
TOTAL RECOMMENDED | $139,493 | $328,600 |
$4,040
82,500
kWh
|
$3,644
-
kW-mo/yr
|
$6,331 |
$2,078
-
MMBtu
|
$37,200 | $(-300.0) | $86,500 | ||
TOTAL IMPLEMENTED | $6,638 | $5,600 |
$2,800
57,200
kWh
|
$2,060
-
kW-mo/yr
|
- |
$2,078
-
MMBtu
|
- | $(-300.0) | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs