| Assessment Year | 2000 |
|---|---|
| Principal Product | Fresh/Frozen Seafood |
| NAICS |
n/a
|
| SIC | 2092: Prepared Fresh or Frozen Fish and Seafoods |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
30,500
ft2
|
| Annual Production | 10,000,000
lb
|
| Production Hrs. Annual | 5,300
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $72,268 | 2,102,579 |
kWh
|
$0.034 |
| Electricity Demand | $22,590 | 81,528 |
kW-mo/yr
|
$0.28 |
| Electricity Fees | $4,771 | - |
|
- |
| LPG | $58,596 | 6,783 |
MMBtu
|
$8.64 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $37,648 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $14,249 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 4.441: Install automatic packing equipment | $10,600 | $58,000 | - | - | - | - | $10,600 | - | - | |
| 02 | 3.4131: Minimize contamination of water before treatment | $9,076 | $12,220 |
$(-390.0)
(-11,430)
kWh
|
$(-152.0)
-
kW-mo/yr
|
- | - | - | $(-602.0) |
$10,220
-
Tgal
|
|
| 03 | 2.1231: Establish burner maintenance schedule for boilers | $7,231 | $600 | - | - | - |
$7,231
-
MMBtu
|
- | - | - | |
| 04 | 2.2621: Modify refrigeration system to operate at a lower pressure | $3,053 | - |
$3,053
88,804
kWh
|
- | - | - | - | - | - | |
| 05 | 2.7124: Make a practice of turning off lights when not needed | $2,380 | - |
$2,380
69,461
kWh
|
- | - | - | - | - | - | |
| 06 | 2.3212: Optimize plant power factor | $670 | $1,900 | - | - | $670 | - | - | - | - | |
| 07 | 2.4133: Use most efficient type of electric motors | $4,638 | $10,431 |
$3,545
103,165
kWh
|
$1,093
-
kW-mo/yr
|
- | - | - | - | - | |
| TOTAL RECOMMENDED | $37,648 | $83,151 |
$8,588
250,000
kWh
|
$941
-
kW-mo/yr
|
$670 |
$7,231
-
MMBtu
|
$10,600 | $(-602.0) |
$10,220
-
Tgal
|
||
| TOTAL IMPLEMENTED | $14,249 | $11,031 |
$5,925
172,626
kWh
|
$1,093
-
kW-mo/yr
|
- |
$7,231
-
MMBtu
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs