Assessment Year | 2000 |
---|---|
Principal Product | Particle Board |
NAICS |
n/a
|
SIC | 2431: Millwork |
Sales Range | $10 M to 50M |
# of Employees | 67 |
Plant Area |
200,000
ft2
|
Annual Production | 37,204
thousand feet
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $460,680 | 10,382,181 |
kWh
|
$0.044 |
Electricity Demand | $106,329 | 232,500 |
kW-mo/yr
|
$0.46 |
Electricity Fees | $4,618 | - |
|
- |
Wood | $778,448 | 304,290 |
MMBtu
|
$2.56 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $365,662 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $240,080 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Wood Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.445: Install equipment to move product | $121,300 | $252,800 |
$(-5,440.0)
(-122,802)
kWh
|
$(-960.0)
-
kW-mo/yr
|
- | - | $127,700 | |
02 | 2.1231: Establish burner maintenance schedule for boilers | $114,832 | $600 | - | - | - |
$114,832
-
MMBtu
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $43,523 | $3,525 |
$40,822
919,988
kWh
|
$2,701
-
kW-mo/yr
|
- | - | - | |
04 | 2.4322: Use or replace with energy efficient substitutes | $38,785 | $45,275 |
$32,748
737,725
kWh
|
$6,037
-
kW-mo/yr
|
- | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $26,070 | $28,457 |
$21,700
488,863
kWh
|
$4,370
-
kW-mo/yr
|
- | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $16,870 | $18,000 |
$14,300
322,098
kWh
|
$2,570
-
kW-mo/yr
|
- | - | - | |
07 | 2.3212: Optimize plant power factor | $4,282 | $11,900 | - | - | $4,282 | - | - | |
TOTAL RECOMMENDED | $365,662 | $360,557 |
$104,130
2,345,872
kWh
|
$14,718
-
kW-mo/yr
|
$4,282 |
$114,832
-
MMBtu
|
$127,700 | ||
TOTAL IMPLEMENTED | $240,080 | $95,857 |
$109,570
2,468,674
kWh
|
$15,678
-
kW-mo/yr
|
- |
$114,832
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Wood Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs