Assessment Year | 1998 |
---|---|
Principal Product | LCD |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 375 |
Plant Area |
160,000
ft2
|
Annual Production | 891,000
pieces
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $358,026 | 16,967,468 |
kWh
|
$0.021 |
Electricity Demand | $104,676 | 26,172 |
kW-mo/yr
|
$4.00 |
Electricity Fees | $11,660 | - |
|
- |
Natural Gas | $71,466 | 16,996 |
MMBtu
|
$4.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $515,578 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,900 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.131: Modify process to reduce material use/cost | $335,710 | $438,500 |
$(-30,650.0)
(-1,452,521)
kWh
|
$(-11,620.0)
-
kW-mo/yr
|
- | $(-12,800.0) | $390,780 | |
02 | 2.6218: Turn off equipment when not in use | $4,900 | - |
$4,900
233,294
kWh
|
- | - | - | - | |
03 | 2.6218: Turn off equipment when not in use | $690 | - |
$690
32,532
kWh
|
- | - | - | - | |
04 | 2.2628: Utilize a less expensive cooling method | $163,740 | $125,000 |
$135,040
6,398,886
kWh
|
- |
$28,700
-
MMBtu
|
- | - | |
05 | 2.3212: Optimize plant power factor | $10,538 | $14,800 |
$10,538
216,882
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $515,578 | $578,300 |
$120,518
5,429,073
kWh
|
$(-11,620.0)
-
kW-mo/yr
|
$28,700
-
MMBtu
|
$(-12,800.0) | $390,780 | ||
TOTAL IMPLEMENTED | $4,900 | - |
$4,900
233,294
kWh
|
- | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs