Assessment Year 1997
Principal Product Milk, Ice Cream, Cottage Cheese
NAICS
n/a
SIC 2026: Fluid Milk
Sales Range $10
M
to 50
M
# of Employees 120
Plant Area 85,236
ft2
Annual Production 164,989,620
lb
Production Hrs. Annual 3,536
hrs
Location (State) Oregon

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $360,454 10,989,156
kWh
Electricity Demand $91,660 515,124
kW-mo/yr
Electricity Fees $27,638 -
Natural Gas $72,106 26,581
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $432,773 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $148,901

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings Solid Waste (non-haz) Savings Personnel Changes Savings Ancillary Material Cost Savings
01 3.4151: Minimize water usage $277,700 $336,500 $(-10,900.0)
(-332,943)
kWh
$(-6,400.0)
-
kW-mo/yr
- - $295,000
-
Tgal
- - -
02 3.5311: Recover and reuse waste material $2,215 - - - - - - $2,215
-
lb
- -
03 3.5311: Recover and reuse waste material $1,880 - - - - - - $1,880
-
lb
- -
04 3.5311: Recover and reuse waste material $1,275 - - - - - - $1,275
-
lb
- -
05 2.2611: Moderate cooling tower outlet temperature $34,550 $24,000 $42,550
1,297,186
kWh
- - - - - - $(-8,000.0)
06 2.2611: Moderate cooling tower outlet temperature $5,800 - $5,800
177,022
kWh
- - - - - - -
07 2.2611: Moderate cooling tower outlet temperature $24,530 $7,000 $24,530
747,948
kWh
- - - - - - -
08 2.4133: Use most efficient type of electric motors $8,751 $20,994 $6,566
200,176
kWh
$2,185
-
kW-mo/yr
- - - - - -
09 2.2121: Increase amount of condensate returned $6,850 $4,200 - - - $6,850
-
MMBtu
- - - -
10 2.3212: Optimize plant power factor $2,682 $18,000 - - $2,682 - - - - -
11 4.311: Schedule deliveries according to demand $4,240 - - - - - - - $4,240 -
12 4.311: Schedule deliveries according to demand $62,300 $51,600 $(-125.0)
(-3,810)
kWh
$(-220.0)
-
kW-mo/yr
- - - - $62,645 -
TOTAL RECOMMENDED $432,773 $462,294 $68,421
2,085,579
kWh
$(-4,435.0)
-
kW-mo/yr
$2,682 $6,850
-
MMBtu
$295,000
-
Tgal
$5,370
-
lb
$66,885 $(-8,000.0)
TOTAL IMPLEMENTED $148,901 $107,794 $79,321
2,418,522
kWh
$1,965
-
kW-mo/yr
- $6,850
-
MMBtu
- $1,880
-
lb
$66,885 $(-8,000.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings Solid Waste (non-haz) Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs