Assessment Year | 1997 |
---|---|
Principal Product | Milk, Ice Cream, Cottage Cheese |
NAICS |
n/a
|
SIC | 2026: Fluid Milk |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
85,236
ft2
|
Annual Production | 164,989,620
lb
|
Production Hrs. Annual | 3,536
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $360,454 | 10,989,156 |
kWh
|
$0.033 |
Electricity Demand | $91,660 | 515,124 |
kW-mo/yr
|
$0.18 |
Electricity Fees | $27,638 | - |
|
- |
Natural Gas | $72,106 | 26,581 |
MMBtu
|
$2.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $432,773 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $148,901 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 3.4151: Minimize water usage | $277,700 | $336,500 |
$(-10,900.0)
(-332,943)
kWh
|
$(-6,400.0)
-
kW-mo/yr
|
- | - |
$295,000
-
Tgal
|
- | - | - | |
02 | 3.5311: Recover and reuse waste material | $2,215 | - | - | - | - | - | - |
$2,215
-
lb
|
- | - | |
03 | 3.5311: Recover and reuse waste material | $1,880 | - | - | - | - | - | - |
$1,880
-
lb
|
- | - | |
04 | 3.5311: Recover and reuse waste material | $1,275 | - | - | - | - | - | - |
$1,275
-
lb
|
- | - | |
05 | 2.2611: Moderate cooling tower outlet temperature | $34,550 | $24,000 |
$42,550
1,297,186
kWh
|
- | - | - | - | - | - | $(-8,000.0) | |
06 | 2.2611: Moderate cooling tower outlet temperature | $5,800 | - |
$5,800
177,022
kWh
|
- | - | - | - | - | - | - | |
07 | 2.2611: Moderate cooling tower outlet temperature | $24,530 | $7,000 |
$24,530
747,948
kWh
|
- | - | - | - | - | - | - | |
08 | 2.4133: Use most efficient type of electric motors | $8,751 | $20,994 |
$6,566
200,176
kWh
|
$2,185
-
kW-mo/yr
|
- | - | - | - | - | - | |
09 | 2.2121: Increase amount of condensate returned | $6,850 | $4,200 | - | - | - |
$6,850
-
MMBtu
|
- | - | - | - | |
10 | 2.3212: Optimize plant power factor | $2,682 | $18,000 | - | - | $2,682 | - | - | - | - | - | |
11 | 4.311: Schedule deliveries according to demand | $4,240 | - | - | - | - | - | - | - | $4,240 | - | |
12 | 4.311: Schedule deliveries according to demand | $62,300 | $51,600 |
$(-125.0)
(-3,810)
kWh
|
$(-220.0)
-
kW-mo/yr
|
- | - | - | - | $62,645 | - | |
TOTAL RECOMMENDED | $432,773 | $462,294 |
$68,421
2,085,579
kWh
|
$(-4,435.0)
-
kW-mo/yr
|
$2,682 |
$6,850
-
MMBtu
|
$295,000
-
Tgal
|
$5,370
-
lb
|
$66,885 | $(-8,000.0) | ||
TOTAL IMPLEMENTED | $148,901 | $107,794 |
$79,321
2,418,522
kWh
|
$1,965
-
kW-mo/yr
|
- |
$6,850
-
MMBtu
|
- |
$1,880
-
lb
|
$66,885 | $(-8,000.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs