| Assessment Year | 1994 |
|---|---|
| Principal Product | Milk |
| NAICS |
n/a
|
| SIC | 2026: Fluid Milk |
| Sales Range | $10 M to 50M |
| # of Employees | 54 |
| Plant Area |
42,000
ft2
|
| Annual Production | 65,000,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $98,912 | 3,112,544 |
kWh
|
$0.032 |
| Natural Gas | $23,857 | 5,300 |
MMBtu
|
$4.50 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $26,705 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,648 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2625: Chill water to the highest temperature possible | $11,122 | $5,000 |
$11,122
386,870
kWh
|
- | |
| 02 | 2.2621: Modify refrigeration system to operate at a lower pressure | $912 | $3,000 |
$912
40,445
kWh
|
- | |
| 03 | 2.2437: Recover waste heat from equipment | $7,860 | $8,997 | - |
$7,860
-
MMBtu
|
|
| 04 | 2.3212: Optimize plant power factor | $4,057 | $5,100 |
$4,057
-
kWh
|
- | |
| 05 | 2.2136: Install / repair insulation on steam lines | $2,378 | $1,394 | - |
$2,378
-
MMBtu
|
|
| 06 | 2.4133: Use most efficient type of electric motors | $376 | $1,075 |
$376
11,723
kWh
|
- | |
| TOTAL RECOMMENDED | $26,705 | $24,566 |
$16,467
439,038
kWh
|
$10,238
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $22,648 | $19,466 |
$12,410
439,038
kWh
|
$10,238
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs