| Assessment Year | 1993 |
|---|---|
| Principal Product | Food cans |
| NAICS |
n/a
|
| SIC | 3411: Metal Cans |
| Sales Range | $10 M to 50M |
| # of Employees | 45 |
| Plant Area |
n/a
|
| Annual Production | 150,000,000
pieces
|
| Production Hrs. Annual | 3,984
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $79,172 | 2,662,954 |
kWh
|
$0.030 |
| Natural Gas | $50,301 | 11,587 |
MMBtu
|
$4.34 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $13,404 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $2,460 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $357 | - |
$357
10,258
kWh
|
- | - | |
| 02 | 2.2437: Recover waste heat from equipment | $10,185 | $10,923 | - |
$10,185
-
MMBtu
|
- | |
| 03 | 2.6218: Turn off equipment when not in use | $445 | $750 |
$445
14,068
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $759 | $1,359 |
$603
21,102
kWh
|
- | $156 | |
| 05 | 2.3212: Optimize plant power factor | $1,458 | $2,700 |
$1,458
-
kWh
|
- | - | |
| 06 | 2.4133: Use most efficient type of electric motors | $200 | $994 |
$200
5,569
kWh
|
- | - | |
| TOTAL RECOMMENDED | $13,404 | $16,726 |
$3,063
50,997
kWh
|
$10,185
-
MMBtu
|
$156 | ||
| TOTAL IMPLEMENTED | $2,460 | $4,444 |
$2,460
29,895
kWh
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs