Assessment Year | 1993 |
---|---|
Principal Product | KIln Dried Lumber |
NAICS |
n/a
|
SIC | 2421: Sawmills and Planing Mills, General |
Sales Range | $500 k to 1M |
# of Employees | 13 |
Plant Area |
n/a
|
Annual Production | 8,395,000
thousand feet
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $7,881 | 264,361 |
kWh
|
$0.030 |
Natural Gas | $43,006 | 13,657 |
MMBtu
|
$3.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $3,951 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,216 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2123: Insulate feedwater tank | $246 | $115 | - |
$246
-
MMBtu
|
- | |
02 | 2.1232: Keep boiler tubes clean | $1,216 | $1,000 | - |
$1,216
-
MMBtu
|
- | |
03 | 2.3212: Optimize plant power factor | $283 | $270 |
$283
-
kWh
|
- | - | |
04 | 2.7141: Lower light fixtures in high ceiling areas | $294 | $757 |
$234
8,206
kWh
|
- | $60 | |
05 | 2.4133: Use most efficient type of electric motors | $39 | $134 |
$39
1,465
kWh
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $208 | $1,550 |
$208
7,913
kWh
|
- | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,665 | $16,830 |
$1,665
76,495
kWh
|
- | - | |
TOTAL RECOMMENDED | $3,951 | $20,656 |
$2,429
94,079
kWh
|
$1,462
-
MMBtu
|
$60 | ||
TOTAL IMPLEMENTED | $1,216 | $1,000 | - |
$1,216
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs