| Assessment Year | 1987 | 
|---|---|
| Principal Product | DAIRY PRODUCTS. | 
| NAICS | 
                             n/a 
                     | 
    
| SIC | 2026: Fluid Milk | 
| Sales Range | $10 M  to 50M  | 
    
| # of Employees | 32 | 
| Plant Area | 
                             n/a 
                     | 
    
| Annual Production | 57,000,000
             
lb
 
         | 
    
| Production Hrs. Annual | 8,736
             
hrs
 
         | 
    
| Location (State) | Oregon | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $75,728 | 1,527,257 | 
             
kWh
 
         | 
        $0.050 | 
| Natural Gas | $44,036 | 10,769 | 
             
MMBtu
 
         | 
        $4.09 | 
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $22,556 | 
             See individual recommendations below 
            *Non-energy impacts included in savings.
         | 
    ||
| IMPLEMENTED SAVINGS* | $6,343 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | 
|---|---|---|---|---|---|---|
| 01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $4,976 | - | 
                        $4,976
                                                     100,528
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $545 | - | 
                        $545
                                                     11,137
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $819 | $326 | 
                        $819
                                                     16,413
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $822 | $300 | - | 
                        $822
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| 05 | 2.2437: Recover waste heat from equipment | $6,675 | $132 | 
                        $135
                                                     2,638
                                 
                                            
kWh
 
                             | 
                                                                                
                        $6,540
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| 06 | 2.2414: Use waste heat from hot flue gases to preheat | $2,968 | $2,925 | - | 
                        $2,968
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| 07 | 2.4133: Use most efficient type of electric motors | $179 | $208 | 
                        $179
                                                     3,517
                                 
                                            
kWh
 
                             | 
                                                                                - | |
| 08 | 2.1213: Direct warmest air to combustion intake | $551 | $600 | - | 
                        $551
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| 09 | 2.7292: Lower ceiling to reduce conditioned space | $5,021 | $8,513 | - | 
                        $5,021
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| TOTAL RECOMMENDED | $22,556 | $13,004 | 
                        $6,654
                                                     134,233
                                 
                                            
kWh
 
                             | 
                                                                                
                        $15,902
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    ||
| TOTAL IMPLEMENTED | $6,343 | $300 | 
                        $5,521
                                                     111,665
                                 
                                            
kWh
 
                             | 
                                                                                
                        $822
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs