Assessment Year 2025
Principal Product HVAC units for RVs
NAICS 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen
SIC 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment
Sales Range $100
M
to 500
M
# of Employees 368
Plant Area 156,000
ft2
Annual Production 450,000
units
Production Hrs. Annual 2,860
hrs
Location (State) Kansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $206,058 2,943,688
kWh
Electricity Demand $173,533 10,250
kW-mo/yr
Electricity Fees $44,305 -
Natural Gas $42,442 4,321
MMBtu
Other Gas $6,372 1
MMBtu
Waste Disposal Costs
Water Usage $16,594 1,720
Tgal
Water Disposal $6,723 1,354
Tgal
Other Liquid (non-haz) $991 1
gal
TOTAL YEARLY COSTS $497,018
RECOMMENDED SAVINGS* $64,431 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,489 $1,176 $5,489
78,420
kWh
- - -
02 2.4231: Reduce the pressure of compressed air to the minimum required $687 - $687
9,820
kWh
- - -
03 2.2437: Recover waste heat from equipment $2,712 $1,080 - - $2,712
-
MMBtu
-
04 2.4239: Eliminate or reduce compressed air usage $5,012 - $5,012
71,593
kWh
- - -
05 2.3212: Optimize plant power factor $15,914 $8,034 - - - $15,914
06 2.8121: Apply for tax-free status for energy purchases $17,308 - - - - $17,308
07 2.7142: Utilize higher efficiency lamps and/or ballasts $6,474 $13,679 $3,003
42,902
kWh
$3,471
-
kW-mo/yr
- -
08 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $10,835 $21,094 $10,835
154,779
kWh
- - -
TOTAL RECOMMENDED $64,431 $45,063 $25,026
357,514
kWh
$3,471
-
kW-mo/yr
$2,712
-
MMBtu
$33,222
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs