Assessment Year 2024
Principal Product Copper Bus bars, Connectors, Terminal Plates
NAICS 335931: Current-Carrying Wiring Device Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range $10
M
to 50
M
# of Employees 95
Plant Area 65,000
ft2
Annual Production 1,772,111
pieces
Production Hrs. Annual 4,160
hrs
Location (State) Arkansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $98,388 1,012,860
kWh
Electricity Demand $42,027 4,452
kW-mo/yr
Natural Gas $37,486 4,487
MMBtu
Waste Disposal Costs
Water Usage $4,796 1,429
Tgal
Water Disposal $16,139 1,429
Tgal
TOTAL YEARLY COSTS $198,836
RECOMMENDED SAVINGS* $51,894 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Administrative Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $878 $1,370 $689
7,104
kWh
$189
-
kW-mo/yr
- - -
02 2.9114: Use solar heat to make electricty $23,461 $163,800 $23,461
241,864
kWh
- - - -
03 2.3212: Optimize plant power factor $5,711 $4,416 - - $5,711 - -
04 2.8117: Install sub-metering equipment $677 $990 - - - - $677
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $10,253 $7,180 $10,253
105,700
kWh
- - - -
06 2.7231: Use radiant heater for spot heating $10,095 $25,179 - - - $10,095
-
MMBtu
-
07 2.6211: Conserve energy by efficient use of vending machines $819 $480 $819
8,439
kWh
- - - -
TOTAL RECOMMENDED $51,894 $203,415 $35,222
363,107
kWh
$189
-
kW-mo/yr
$5,711 $10,095
-
MMBtu
$677
TOTAL IMPLEMENTED - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs