| Assessment Year | 2024 |
|---|---|
| Principal Product | Electronic engine & Motion control assemblies |
| NAICS | 334412: Bare Printed Circuit Board Manufacturing |
| SIC | 3672: Printed Circuit Boards |
| Sales Range | $100 M to 500M |
| # of Employees | 259 |
| Plant Area |
185,000
ft2
|
| Annual Production | 2,416,616
pieces
|
| Production Hrs. Annual | 5,600
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $378,967 | 3,439,760 |
kWh
|
$0.11 | |
| Natural Gas | $9,697 | 2,604 |
MMBtu
|
$3.72 | |
| Waste Disposal Costs | |||||
| Water Usage | $3,544 | 1,185 |
Tgal
|
$2.99 | |
| Water Disposal | $11,931 | 1,185 |
Tgal
|
$10.07 | |
| TOTAL YEARLY COSTS | $404,139 | ||||
| RECOMMENDED SAVINGS* | $90,304 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $33,792 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7135: Install occupancy sensors | $196 | $563 |
$196
1,778
kWh
|
- | |
| 02 | 2.6211: Conserve energy by efficient use of vending machines | $378 | $178 |
$378
3,440
kWh
|
- | |
| 03 | 2.9114: Use solar heat to make electricty | $56,512 | $327,600 |
$56,512
513,743
kWh
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,975 | $5,473 |
$7,975
72,504
kWh
|
- | |
| 05 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $13,497 | $142,202 |
$9,252
84,102
kWh
|
$4,245
-
MMBtu
|
|
| 06 | 2.7211: Clean and maintain refrigerant condensers and towers | $8,042 | $13,524 |
$8,042
73,106
kWh
|
- | |
| 07 | 2.7232: Replace existing hvac unit with high efficiency model | $2,757 | $7,700 |
$2,757
25,062
kWh
|
- | |
| 08 | 2.6218: Turn off equipment when not in use | $947 | - |
$947
8,610
kWh
|
- | |
| TOTAL RECOMMENDED | $90,304 | $497,240 |
$86,059
782,345
kWh
|
$4,245
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $33,792 | $169,640 |
$29,547
268,602
kWh
|
$4,245
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs