| Assessment Year | 2023 |
|---|---|
| Principal Product | aircraft parts & part refurbishment |
| NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
| SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 292 |
| Plant Area |
117,000
ft2
|
| Annual Production | 30,000
units
|
| Production Hrs. Annual | 3,640
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $357,802 | 2,819,600 |
kWh
|
$0.13 | |
| Natural Gas | $5,814 | 2,741 |
MMBtu
|
$2.12 | |
| Waste Disposal Costs | |||||
| Water Usage | $6,484 | 1,426 |
Tgal
|
$4.55 | |
| Water Disposal | $13,536 | 1,426 |
Tgal
|
$9.49 | |
| Solid Waste (non-haz) | $9,457 | 925,338 |
lb
|
$0.010 | |
| TOTAL YEARLY COSTS | $393,093 | ||||
| RECOMMENDED SAVINGS* | $110,701 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $6,760 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7135: Install occupancy sensors | $1,017 | $630 |
$1,017
7,826
kWh
|
- | |
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $3,533 | $9,900 |
$3,533
27,178
kWh
|
- | |
| 03 | 2.7229: Air condition only space necessary | $17,766 | - |
$17,766
136,660
kWh
|
- | |
| 04 | 2.9114: Use solar heat to make electricty | $86,175 | $394,200 |
$86,175
662,888
kWh
|
- | |
| 05 | 2.3212: Optimize plant power factor | $2,210 | $9,834 | - | $2,210 | |
| TOTAL RECOMMENDED | $110,701 | $414,564 |
$108,491
834,552
kWh
|
$2,210 | ||
| TOTAL IMPLEMENTED | $6,760 | $20,364 |
$4,550
35,004
kWh
|
$2,210 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs