| Assessment Year | 2020 |
|---|---|
| Principal Product | Machined components |
| NAICS | 332710: Machine Shops |
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 35 |
| Plant Area |
143,000
ft2
|
| Annual Production | 7,000
units
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $38,740 | 1,527,352 |
kWh
|
$0.025 | |
| Electricity Demand | $69,349 | 5,629 |
kW-mo/yr
|
$12.32 | |
| Electricity Fees | $1,200 | - |
|
- | |
| Natural Gas | $13,388 | 2,981 |
MMBtu
|
$4.49 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,262 | 611 |
Tgal
|
$3.70 | |
| TOTAL YEARLY COSTS | $124,939 | ||||
| RECOMMENDED SAVINGS* | $15,582 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $417 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $10,720 | $12,215 | - | - | $10,720 | - | |
| 02 | 2.7231: Use radiant heater for spot heating | $4,244 | $3,000 | - | - | - |
$4,244
-
MMBtu
|
|
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $417 | $1,804 |
$146
5,610
kWh
|
$271
-
kW-mo/yr
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $201 | $1,049 |
$201
7,710
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $15,582 | $18,068 |
$347
13,320
kWh
|
$271
-
kW-mo/yr
|
$10,720 |
$4,244
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $417 | $1,804 |
$146
5,610
kWh
|
$271
-
kW-mo/yr
|
- | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs