Assessment Year | 2020 |
---|---|
Principal Product | Wire harnesses |
NAICS | 335931: Current-Carrying Wiring Device Manufacturing |
SIC | 3643: Current-Carrying Wiring Devices |
Sales Range | $50 M to 100M |
# of Employees | 185 |
Plant Area |
112,500
ft2
|
Annual Production | 39,000
units
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $63,334 | 1,583,338 |
kWh
|
$0.040 | |
Electricity Demand | $36,950 | 3,278 |
kW-mo/yr
|
$11.27 | |
Electricity Fees | $11,755 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $3,011 | 833 |
Tgal
|
$3.61 | |
TOTAL YEARLY COSTS | $115,050 | ||||
RECOMMENDED SAVINGS* | $18,507 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $13,449 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,568 | $2,250 |
$1,568
39,201
kWh
|
- | |
02 | 2.6218: Turn off equipment when not in use | $4,512 | - |
$4,512
112,795
kWh
|
- | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $4,684 | $22,100 |
$2,227
55,679
kWh
|
$2,457
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,197 | $30,672 |
$4,086
102,155
kWh
|
$3,111
-
kW-mo/yr
|
|
05 | 2.6218: Turn off equipment when not in use | $546 | $522 |
$546
13,650
kWh
|
- | |
TOTAL RECOMMENDED | $18,507 | $55,544 |
$12,939
323,480
kWh
|
$5,568
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $13,449 | $55,022 |
$7,881
197,035
kWh
|
$5,568
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs