| Assessment Year | 2015 |
|---|---|
| Principal Product | Hand Tools |
| NAICS | 332216: Saw Blade and Handtool Manufacturing |
| SIC | 3423: Hand and Edge Tools, Except Machine Tools and Handsaws |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
104,258
ft2
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $229,401 | 4,063,332 |
kWh
|
$0.056 |
| Electricity Demand | $98,727 | 15,671 |
kW-mo/yr
|
$6.30 |
| Natural Gas | $14,903 | 3,346 |
MMBtu
|
$4.45 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $87,666 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $34,366 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $950 | $580 |
$950
16,825
kWh
|
- | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,502 | $30,324 |
$5,345
95,441
kWh
|
$1,157
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,204 | $77,600 |
$20,744
370,432
kWh
|
$4,460
-
kW-mo/yr
|
- | - | |
| 04 | 2.3212: Optimize plant power factor | $37,221 | $46,451 | - | - | $37,221 | - | |
| 05 | 2.7231: Use radiant heater for spot heating | $2,132 | $6,660 | - | - | - |
$2,132
-
MMBtu
|
|
| 06 | 2.2628: Utilize a less expensive cooling method | $10,800 | $22,080 |
$8,154
145,600
kWh
|
$2,646
-
kW-mo/yr
|
- | - | |
| 07 | 2.7211: Clean and maintain refrigerant condensers and towers | $2,660 | $720 |
$1,469
26,225
kWh
|
$1,191
-
kW-mo/yr
|
- | - | |
| 08 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,542 | $780 |
$1,542
27,534
kWh
|
- | - | - | |
| 09 | 2.6211: Conserve energy by efficient use of vending machines | $656 | $690 |
$656
11,618
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $87,666 | $185,885 |
$38,859
693,675
kWh
|
$9,455
-
kW-mo/yr
|
$37,221 |
$2,132
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $34,366 | $108,644 |
$27,558
492,098
kWh
|
$6,809
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs