Assessment Year 2014
Principal Product Investment castings
NAICS 331523: Nonferrous Metal Die-Casting Foundries
SIC 3324: Steel Investment Foundries
Sales Range $5
M
to 10
M
# of Employees 54
Plant Area 20,000
ft2
Annual Production 28,600
pieces
Production Hrs. Annual 5,850
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $185,308 1,546,500
kWh
Natural Gas $30,563 6,728
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $62,962 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $26,107

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $23,245 - $23,245
193,708
kWh
-
02 2.4322: Use or replace with energy efficient substitutes $2,223 $1,540 $2,223
18,528
kWh
-
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,460 $2,969 $11,460
95,500
kWh
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $652 $3,540 $652
5,437
kWh
-
05 2.7241: Install outside air damper / economizer on hvac unit $8,810 $4,000 $8,810
73,416
kWh
-
06 2.7211: Clean and maintain refrigerant condensers and towers $52 $30 $52
430
kWh
-
07 2.7224: Reduce space conditioning during non-working hours $700 $120 - $700
-
MMBtu
08 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $487 $1,834 $487
4,057
kWh
-
09 2.1135: Repair furnaces and oven doors so that they seal efficiently $2,159 $1,600 - $2,159
-
MMBtu
10 2.2437: Recover waste heat from equipment $6,815 $55,000 - $6,815
-
MMBtu
11 2.2414: Use waste heat from hot flue gases to preheat $3,984 $17,104 - $3,984
-
MMBtu
12 2.2414: Use waste heat from hot flue gases to preheat $2,375 $5,900 - $2,375
-
MMBtu
TOTAL RECOMMENDED $62,962 $93,636 $46,929
391,077
kWh
$16,033
-
MMBtu
TOTAL IMPLEMENTED $26,107 $5,170 $23,949
199,575
kWh
$2,159
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs