Assessment Year | 2006 |
---|---|
Principal Product | PVC Resin |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $100 M to 500M |
# of Employees | 100 |
Plant Area |
100,000
ft2
|
Annual Production | 500,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $907,992 | 133,150 |
kWh
|
$6.82 |
Electricity Demand | $333,533 | 62,512 |
kW-mo/yr
|
$5.34 |
Natural Gas | $3,996,595 | 202,258 |
MMBtu
|
$19.76 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $181,880 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2163: Use minimum steam operating pressure | $22,707 | $1,420 | - | - |
$22,707
-
MMBtu
|
|
02 | 2.2121: Increase amount of condensate returned | $7,798 | $11,625 | - | - |
$7,798
-
MMBtu
|
|
03 | 2.2113: Repair or replace steam traps | $92,687 | $1,025 | - | - |
$92,687
-
MMBtu
|
|
04 | 2.4239: Eliminate or reduce compressed air usage | $30,440 | $19,260 |
$23,884
628,530
kWh
|
$6,556
-
kW-mo/yr
|
- | |
05 | 2.2611: Moderate cooling tower outlet temperature | $28,248 | $15,000 |
$28,248
743,374
kWh
|
- | - | |
TOTAL RECOMMENDED | $181,880 | $48,330 |
$52,132
1,371,904
kWh
|
$6,556
-
kW-mo/yr
|
$123,192
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |