Assessment Year | 2004 |
---|---|
Principal Product | Pizza Crust |
NAICS | 311412: Frozen Specialty Food Manufacturing |
SIC | 2038: Frozen Specialties, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 90 |
Plant Area |
48,000
ft2
|
Annual Production | 12,000,000
lb
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $101,313 | 3,544,466 |
kWh
|
$0.029 |
Electricity Demand | $75,406 | 9,050 |
kW-mo/yr
|
$8.33 |
Electricity Fees | $50,366 | - |
|
- |
Natural Gas | $19,293 | 2,014 |
MMBtu
|
$9.58 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $91,295 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,553 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7425: Clean or color roof to reduce solar load | $35,493 | $329,564 |
$35,493
553,718
kWh
|
- | - | - | - | - | - | |
02 | 2.2437: Recover waste heat from equipment | $17,436 | $17,500 | - | - | - |
$17,436
-
MMBtu
|
- | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,386 | $4,515 |
$1,386
48,444
kWh
|
- | - | - | - | - | - | |
04 | 2.7241: Install outside air damper / economizer on hvac unit | $10,723 | $21,750 |
$10,723
374,912
kWh
|
- | - | - | - | - | - | |
05 | 2.8112: Combine utility meters | $2,354 | $2,546 | - | - | $1,612 | - | - | $742 | - | |
06 | 2.4156: Establish a preventative maintenance program | $6,830 | - | - | - | - | - | $6,830 | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,073 | $23,985 |
$11,472
178,963
kWh
|
$4,296
-
kW-mo/yr
|
- | - | $4,950 | - | $(-3,645.0) | |
TOTAL RECOMMENDED | $91,295 | $399,860 |
$59,074
1,156,037
kWh
|
$4,296
-
kW-mo/yr
|
$1,612 |
$17,436
-
MMBtu
|
$11,780 | $742 | $(-3,645.0) | ||
TOTAL IMPLEMENTED | $17,553 | $21,750 |
$10,723
374,912
kWh
|
- | - | - | $6,830 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs