Assessment Year | 1994 |
---|---|
Principal Product | Fixtures and furniture |
NAICS |
n/a
|
SIC | 2521: Wood Office Furniture |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
80,000
ft2
|
Annual Production | 16,000
pieces
|
Production Hrs. Annual | 6,816
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,311 | 1,664,127 |
kWh
|
$0.052 |
Natural Gas | $25,336 | 8,424 |
MMBtu
|
$3.01 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,267 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,654 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,568 | $4,848 |
$1,568
17,585
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,701 | $12,214 |
$3,701
46,893
kWh
|
- | |
03 | 2.7135: Install occupancy sensors | $187 | $200 |
$187
4,982
kWh
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $665 | $851 |
$665
17,585
kWh
|
- | |
05 | 2.2437: Recover waste heat from equipment | $1,114 | $800 | - |
$1,114
-
MMBtu
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $766 | - |
$766
24,033
kWh
|
- | |
07 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $1,266 | $3,750 |
$1,266
33,411
kWh
|
- | |
TOTAL RECOMMENDED | $9,267 | $22,663 |
$8,153
144,489
kWh
|
$1,114
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,654 | $12,414 |
$4,654
75,908
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs