Assessment Year | 1992 |
---|---|
Principal Product | STAINLESS STEEL TUBING |
NAICS |
n/a
|
SIC | 3317: Steel Pipe and Tubes |
Sales Range | $10 M to 50M |
# of Employees | 56 |
Plant Area |
n/a
|
Annual Production | 21,000
thousand feet
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $187,896 | 2,980,363 |
kWh
|
$0.063 |
Natural Gas | $7,129 | 1,327 |
MMBtu
|
$5.37 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,156 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,791 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $20,408 | $1,580 |
$20,408
375,733
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,003 | $8,297 |
$5,003
101,407
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,457 | $1,131 |
$3,283
62,134
kWh
|
- | $(-826.0) | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,087 | $1,276 |
$1,087
20,516
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $832 | - |
$832
20,809
kWh
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $615 | $2,279 |
$615
12,309
kWh
|
- | - | |
07 | 2.2437: Recover waste heat from equipment | $612 | $1,922 | - |
$612
-
MMBtu
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $135 | $318 |
$135
2,052
kWh
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7 | $111 |
$21
293
kWh
|
- | $(-14.0) | |
TOTAL RECOMMENDED | $31,156 | $16,914 |
$31,384
595,253
kWh
|
$612
-
MMBtu
|
$(-840.0) | ||
TOTAL IMPLEMENTED | $24,791 | $4,098 |
$25,631
479,485
kWh
|
- | $(-840.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs