Assessment Year | 1987 |
---|---|
Principal Product | CRACKERS AND COOKIES |
NAICS |
n/a
|
SIC | 2052: Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 110 |
Plant Area |
n/a
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 5,200
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $83,597 | 1,875,147 |
kWh
|
$0.045 |
Natural Gas | $116,587 | 37,896 |
MMBtu
|
$3.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,958 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,908 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $479 | $225 |
$479
14,654
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $346 | $88 |
$346
7,913
kWh
|
- | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $1,643 | $80 |
$1,643
38,687
kWh
|
- | |
04 | 2.2122: Install / repair insulation on condensate lines | $204 | $308 | - |
$204
-
MMBtu
|
|
05 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $75 | $99 | - |
$75
-
MMBtu
|
|
06 | 2.2136: Install / repair insulation on steam lines | $1,095 | $2,640 | - |
$1,095
-
MMBtu
|
|
07 | 2.6218: Turn off equipment when not in use | $36 | - |
$36
586
kWh
|
- | |
08 | 2.2437: Recover waste heat from equipment | $1,673 | $306 | - |
$1,673
-
MMBtu
|
|
09 | 2.2221: Use immersion heating in tanks, melting pots, etc | $4,158 | $1,600 |
$(-462.0)
(-10,258)
kWh
|
$4,620
-
MMBtu
|
|
10 | 2.2221: Use immersion heating in tanks, melting pots, etc | $249 | $110 |
$(-28.0)
(-586)
kWh
|
$277
-
MMBtu
|
|
TOTAL RECOMMENDED | $9,958 | $5,456 |
$2,014
50,996
kWh
|
$7,944
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,908 | $3,666 |
$861
23,153
kWh
|
$3,047
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs